MANAGING UTILITY FEEDS AND EMERGENCY POWER

With a Service Entrance Rated Transfer Switch.

The power transfer switch meets all UL and National Electrical Code requirements for a service rated transfer switch or transfer switch/bypass isolation switch. Service entrance rated transfer switches generally are installed at facilities that have a single utility feed and a single emergency power source. A circuit breaker serves as the service disconnect and links are provided to disconnect both neutral and ground connections. The product is designed and manufactured in accordance with UL 891 Switchboard requirements. The transfer switch is UL 1008 listed and is available up to 600V and 4000A in standard, delayed, closed transition, and bypass-isolation configurations. The ASCO 7000 SERIES Service Entrance Rated Transfer Switch combines automatic power switching with an overcurrent service disconnect device on the utility source.

ASCO debuted the first true service entrance transfer switch that integrates the switch and service disconnect.

ASCO 7000 SERIES Service Entrance Rated Transfer Switch

1

2

One line diagram of a typical service entrance rated transfer switch. It’s available with solid, switched or overlapping neu tral poles.

1 GFCT - Ground Fault Current Transformer 2 ATS - Automatic Transfer Switch

22