ASCO Power Technologies Products Digital Binder
ATS Product S ERIES
Comparison Features
185
300 Group G
4000
7000
Voltage and Frequency Settings Phase Selection Pick up Normal Source Voltage Drop out Normal Source Voltage Pick up Emergency Source Voltage Drop out Emergency Source Voltage
Single Phase
Single or Three Phase Single or Three Phase Single or Three Phase
198 Volts
85 to 100% 70% to 98% 85 to 100% 70% to 98% 50 or 60 Hz 95% Fixed 85% Fixed 102 to 115% 102 to 115% 101 to 110% 101 to 110% 86 to 100%
85 to 100% 70% to 98% 85 to 100% 70% to 98% 50 or 60 Hz 90 to 100% 85 to 98% 102 to 115% 102 to 115% 101 to 110% 101 to 110% 90 to 100%
85 to 100% 70% to 98% 85 to 100% 70% to 98% 50 or 60 Hz 90 to 100% 85 to 98% 102 to 115% 102 to 115% 101 to 110% 101 to 110% 90 to 100%
154-187 Volts
198 Volts 165 Volts
Frequency
50 or 60Hz 48 or 57Hz 43 or 51Hz
Pick Up Emergency Source Frequency Drop out Emergency Source Frequency Normal Overvoltage Trip Emergency Overvoltage Trip Normal Overfrequency Trip Emergency Overfrequency Trip Pick up Normal Source Frequency Drop out Normal Source Frequency Normal & Emergency Voltage Unbalance Time Delay Settings Override Normal Source Momentary Outage
N/A N/A N/A N/A N/A N/A N/A
85 to 98%
85 to 98%
85 to 98%
N/A
Yes
Yes
1 or 3 Seconds
0 to 6 Seconds
0 to 6 Seconds 0 to 60 Minutes 0 to 60 Minutes 0 to 60 Minutes 0 to 60 Minutes Programmable
0 to 6 Seconds 0 to 60 Minutes 0 to 60 Minutes 0 to 60 Minutes 0 to 60 Minutes Programmable
Transfer to Emergency
10 Seconds
0 to 60 Min 59 Sec 0 to 60 Min 59 Sec 0 to 60 Min 59 Sec
Re-transfer to Normal Utility Power Loss Mode
5 Minutes
Engine Cool Down
2 or 5 Minutes
Override Emergency Source Momentary Outage
4 Seconds
0 to 6 Seconds
Generator Exerciser
7 Day
7 Day
Indication and Controls Load Connected to Normal Load Connected to Emergency Normal Source Available Emergency Source Available
Yes Yes Yes Yes Yes Yes N/A N/A N/A N/A N/A N/A Yes Yes N/A N/A N/A N/A Yes N/A Yes STD
Yes Yes Yes Yes Yes Yes Yes Yes STD STD
Yes Yes Yes Yes Yes Yes Yes Yes STD
Yes Yes Yes Yes Yes Yes Yes Yes STD
Transfer Test Switch
Terminals For Remote Transfer Control
Bypass Time Delay Switch
Transfer Inhibit In-Phase Monitor
Load Disconnect Contacts with Time Delay
Optional
Optional
Event Log
Optional Optional
Yes
Yes
Power Manager
Optional
Optional Optional
Transfer Controls Lock Out
N/A
Yes
Enclosures Type 1
Yes Yes Yes Yes Yes Yes Yes Yes Yes
Yes Yes Yes Yes Yes Yes Yes Yes Yes
Yes Yes Yes Yes Yes Yes Yes Yes Yes
Type 3R
Type 4
Type 4X Type 12
Connectivity RS-485 Serial
Ethernet Modbus
Monitoring and Control via ASCO Products
Optional Accessories Optional
Field Kits Only
Expanded
Limited
Extensive
www.ascopower.com customercare@ascopower.com • 1-800-800-ASCO (2726) © 2022 Publication 3149 R9
ASCO Power Technologies 160 Park Avenue, Florham Park, NJ 07932
Made with FlippingBook - Online catalogs