ATS Product S ERIES
Comparison Features
185
300
7000
Voltage and Frequency Settings Phase Selection Pick up Normal Source Voltage Drop out Normal Source Voltage Pick up Emergency Source Voltage Drop out Emergency Source Voltage Pick up Normal Source Frequency Drop out Normal Source Frequency Pick Up Emergency Source Frequency Drop out Emergency Source Frequency Nominal Frequency
Single Phase
Single or Three Phase
Single or Three Phase
198 or 209 Volts 154 - 198 Volts
85 to 100% 70 to 98% 85 to 100% 70 to 98% 50 or 60 Hz 86 to 100% 85 to 98% 86 to 100% 85 to 98% 102 to 116% 102 to 116% 101 to 111% 101 to 111%
85 to 100% 70 to 98% 85 to 100% 70 to 98% 50 or 60 Hz 90 to 100% 85 to 98% 90 to 100% 85 to 98% 102 to 115% 102 to 115% 102 to 110% 102 to 110%
198 Volts 165 Volts
50 or 60Hz
- -
48 or 57Hz 43 or 51Hz
Normal Overvoltage Trip Emergency Overvoltage Trip Normal Overfrequency Trip Emergency Overfrequency Trip
- - - - -
Normal & Emergency Voltage Unbalance Time Delay Settings Override Normal Source Momentary Outage
-
Yes
1 or 3 Seconds
0 to 6 Seconds
0 to 6 Seconds 0 to 60 Minutes 0 to 60 Minutes 0 to 60 Minutes 0 to 60 Minutes Programmable
Transfer to Emergency
10 Seconds
0 to 60 Min 59 Sec 0 to 60 Min 59 Sec 0 to 60 Min 59 Sec
Re-transfer to Normal Utility Power Loss Mode
5 Minutes
Engine Cool Down
2 or 5 Minutes
Override Emergency Source Momentary Outage
4 Seconds
0 to 6 Seconds Programmable
Engine Exerciser
7 Day
Indication and Controls Load Connected to Normal Load Connected to Emergency Normal Source Acceptable Emergency Source Acceptable
Yes Yes Yes Yes Yes
Yes Yes Yes Yes Yes Yes Yes Yes STD STD
Yes Yes Yes Yes Yes Yes Yes Yes STD
Transfer Test Switch
Terminals For Remote Transfer Control
STD
Bypass Time Delay Switch
Yes
Transfer Inhibit In-Phase Monitor
- - - - - -
Load Disconnect Contacts with Time Delay
Optional
Event Log
Optional Optional
Yes
Current and Power Metering Transfer Controls Lock Out
Optional Optional
-
Enclosures Type 1
STD
STD
STD
Type 3R
Optional
Optional Optional Optional Optional Optional Optional Optional Optional
Optional Optional Optional Optional Optional Optional Optional Optional
Type 4
- - -
Type 4X Type 12
Connectivity RS-485 Serial
-
Ethernet Modbus
Optional
-
Monitoring and Control via ASCO Products
Optional
Optional Accessories Customization Level
Preconfigured accessory portfolio
Field Kits Only - Limited
Custom Specified