ASCO Power Technologies Products Digital Binder

ATS Product S ERIES

Comparison Features

185

300

7000

Voltage and Frequency Settings Phase Selection Pick up Normal Source Voltage Drop out Normal Source Voltage Pick up Emergency Source Voltage Drop out Emergency Source Voltage Pick up Normal Source Frequency Drop out Normal Source Frequency Pick Up Emergency Source Frequency Drop out Emergency Source Frequency Nominal Frequency

Single Phase

Single or Three Phase

Single or Three Phase

198 or 209 Volts 154 - 198 Volts

85 to 100% 70 to 98% 85 to 100% 70 to 98% 50 or 60 Hz 86 to 100% 85 to 98% 86 to 100% 85 to 98% 102 to 116% 102 to 116% 101 to 111% 101 to 111%

85 to 100% 70 to 98% 85 to 100% 70 to 98% 50 or 60 Hz 90 to 100% 85 to 98% 90 to 100% 85 to 98% 102 to 115% 102 to 115% 102 to 110% 102 to 110%

198 Volts 165 Volts

50 or 60Hz

- -

48 or 57Hz 43 or 51Hz

Normal Overvoltage Trip Emergency Overvoltage Trip Normal Overfrequency Trip Emergency Overfrequency Trip

- - - - -

Normal & Emergency Voltage Unbalance Time Delay Settings Override Normal Source Momentary Outage

-

Yes

1 or 3 Seconds

0 to 6 Seconds

0 to 6 Seconds 0 to 60 Minutes 0 to 60 Minutes 0 to 60 Minutes 0 to 60 Minutes Programmable

Transfer to Emergency

10 Seconds

0 to 60 Min 59 Sec 0 to 60 Min 59 Sec 0 to 60 Min 59 Sec

Re-transfer to Normal Utility Power Loss Mode

5 Minutes

Engine Cool Down

2 or 5 Minutes

Override Emergency Source Momentary Outage

4 Seconds

0 to 6 Seconds Programmable

Engine Exerciser

7 Day

Indication and Controls Load Connected to Normal Load Connected to Emergency Normal Source Acceptable Emergency Source Acceptable

Yes Yes Yes Yes Yes

Yes Yes Yes Yes Yes Yes Yes Yes STD STD

Yes Yes Yes Yes Yes Yes Yes Yes STD

Transfer Test Switch

Terminals For Remote Transfer Control

STD

Bypass Time Delay Switch

Yes

Transfer Inhibit In-Phase Monitor

- - - - - -

Load Disconnect Contacts with Time Delay

Optional

Event Log

Optional Optional

Yes

Current and Power Metering Transfer Controls Lock Out

Optional Optional

-

Enclosures Type 1

STD

STD

STD

Type 3R

Optional

Optional Optional Optional Optional Optional Optional Optional Optional

Optional Optional Optional Optional Optional Optional Optional Optional

Type 4

- - -

Type 4X Type 12

Connectivity RS-485 Serial

-

Ethernet Modbus

Optional

-

Monitoring and Control via ASCO Products

Optional

Optional Accessories Customization Level

Preconfigured accessory portfolio

Field Kits Only - Limited

Custom Specified

ASCO Power Technologies 160 Park Avenue, Florham Park, NJ 07932

www.ascopower.com customercare@ascopower.com • 1-800-800-ASCO (2726) © 2023 Publication 3149 R11

Made with FlippingBook - Online catalogs