ASCO Power Technologies Products Digital Binder
Load Management Strategies The Model 5810 adds ATS loads until the user-config ured threshold is momentarily exceeded, then removes the last ATS added. This strategy offers simple set-up and operation. Before connecting an ATS, the Model 5850 compares available generator capacity to the expected size of the next load, preventing transfers that could exceed overload thresholds. This strategy offers sophisticated control and precise load management.
Generator Rating
5810
Overload Threshold
5850
Generator Loading
Time
Value-Added Features
Manual Overrides
Time Sequencing
Some circumstances could require facilities to force loads off-line or on-line, despite their assigned priority. All 5800 Series models enable users to manually force loads off of the Emergency source and allow supervised requests to connect loads to the Emergency source, regardless of assigned priority.
The ASCO 5850 Load Management Units can cycle individual loads onto and off of Emergency sources for user-defined periods. This allows capacity to sequentially serve multiple loads, providing power to each ATS for a user-defined interval.
Features and Specifications
Model
5810
5850-SG 1193586
5850-DG 1240925
Part Number
1232238
FEATURES
Max Managed ATSs
6 1
8 1
8
Generators
2 (Paralleled)
Operation Principal Time Sequencing
Reactive
Proactive (Bus Optimization) Proactive (Bus Optimization)
No No
Yes Yes
Yes Yes
LED/Audible Alarm Indicators
Interface
Black & White Touch Screen Yes via screen (supervised)
Manual Overrides Communications
Modbus TCP/IP
TECHNICAL SPECIFICATIONS
Primary Control Power Secondary Control Power
120Vac, 60Hz, 2A
24Vdc, 5A
Dimensions (HxWxD)
21" x 21" x 9"
Add/Shed Signal
24 Vdc
Note: A separate ASCO Power Meter is required for each generator. See the ASCO 5210 Digital Power Meter Data Sheet .
For custom load management solutions, contacts a local ASCO sales representative.
www.ascopower.com customercare@ascopower.com • 1-800-800-ASCO (2726) © 2024. Publication 2045 R2
ASCO Power Technologies 160 Park Avenue, Florham Park, NJ 07932