ASCO Power Technologies Products Digital Binder
This document presents electrical ratings and specifications for ASCO transfer switches in accordance Switchgear and Controlgear. For additional information, contact an authorized ASCO representative.
Short-Circuit Ratings
Current Range (Ie) A
IEC Utilization Category
Voltage (Ue) V
Short Time Withstand Current (Icw)
Short-Circuit Making Capacity (Icm)
Conditiona Short-Circu Rating(lq)
Frame
Icq = 10kA w LPS - RK - 400 S
AC-33B
30 - 200
18.9kA
110 - 440
AC-32A
225
10kA for 31 ms (for main poles)
Ip = 12.3kA
D
AC-33A
30 - 100
480
18.0kA
I2t = 284 x 10E3 (Overlapping Ne
AC-32A
150 - 225
AC-33A 15kA for 60 ms
35kA
150 - 400
J
110 - 440
--
600
AC-32A 12kA for 50 ms
27kA
AC-33A 36kA for 378 ms (All)
600 - 1000
30kA for 500 ms (600-800A TSE ) (600-1200A Bypass)
84.1kA
--
208 - 440
H
1200
AC-33B
AC-33A
1600
50kA for 56 ms 42kA for 307 ms for all
123.4kA
--
2000 - 3000 AC-32A
G 208 - 440
85kA for 135 ms 65kA for 500 ms for all
3200 - 4000
AC-32A
192kA
--
Notes; For additional dimension and venting details, please refer to the Outline Drawing for each model. TSE = Transfer Switch Equipment Bypass = Bypass Isolation Transfer Switch Equipment
Made with FlippingBook - Online catalogs